Title :
Partial discharge characteristics of oil-immersed insulation systems under DC, combined AC-DC and DC reversed polarity voltage
Author :
Takahashi, E. ; Tsutsumi, Y. ; Okuyama, K. ; Ogata, F.
Author_Institution :
Hitachi Ltd., Ibaraki-ken, Japan
Abstract :
Breakdown characteristics of insulating oil, under combined ac-dc voltage and dc reversed polarity voltage, and partial discharge characteristics of oil-immersed insulation, under combined ac-dc voltage and polarity revesal of dc voltage Were made clear by elementary experiments. After that, a numerical dc field mapping method for electric field analysis of two-dimensional configurations which consist of composite insulation and field mapping methods under combined ac-dc voltage and dc reversed polarity voltage were proposed. Futhermore, partial discharge characteristics of transformer insulation under dc, combined ac-dc voltage were experimentally made clear by practical trial models.
Keywords :
Breakdown voltage; Electrodes; Moisture; Oil insulation; Partial discharges; Petroleum; Power transformer insulation; Testing; Thyristors; Valves;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1976.32119