• DocumentCode
    851533
  • Title

    Investigation on the physical phenomena around current zero in HV gas blast breakers

  • Author

    Hermann, W. ; Kogelschatz, U. ; Niemeyer, L. ; Ragaller, K. ; Schade, E.

  • Author_Institution
    Brown Boveri Research Center, Baden, Switzerland
  • Volume
    95
  • Issue
    4
  • fYear
    1976
  • fDate
    7/1/1976 12:00:00 AM
  • Firstpage
    1165
  • Lastpage
    1176
  • Abstract
    An axially blown arc is studied under physical conditions typical of HV circuit breakers. The experiment is especially designed to produce a stable and reproducible arc with good accessability for diagnostics. After a stationary phase the current is ramped down with adjustable slope. The vicinity of current zero is especially investigated. For the first time, the most effective recovery zone is localized and its physical parameters are evaluated. The limiting curve for thermal reignition is determined. Based on the observed phenomena a theoretical description is derived which explains quite well the experimentally known extinction characteristics of this type of arc.
  • Keywords
    Circuit breakers; Electrodes; Ignition; Meetings; Power & Energy Society; Printing; Sparks; Switchgear; Voltage; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32210
  • Filename