• DocumentCode
    851792
  • Title

    HTGR performance under adverse network conditions

  • Author

    Rodriguez, L.A. ; Waxberg, H. ; Watkins, H.E.

  • Author_Institution
    Ebasco Services Incorporated, New York, New York
  • Volume
    95
  • Issue
    4
  • fYear
    1976
  • fDate
    7/1/1976 12:00:00 AM
  • Firstpage
    1403
  • Lastpage
    1412
  • Abstract
    This paper analyzes the performance of the auxiliary systems of High Temperature Gas Reactor (HTGR) Reference Plant under conditions of degraded electrical network supply resulting from certain postulated power system disturbances. Specifically, an attempt is made to identify the particular conditions of non-standard frequence and/or voltage at which the generator´s capability to produce power starts to decrease and, if such condition exists, to identify the particular equipment (electrical or mechanical) whose performance is causing the limitation. A discussion of the effects arising from specified changes of voltage and/or frequency on plant operation is presented. A set of degraded electrical network supply conditions has been assumed to have originated from system switching, load changes or due to abrupt loss of major generation, transmission lines or major interconnecting ties.
  • Keywords
    Degradation; Frequency; Inductors; Performance analysis; Power generation; Power system analysis computing; Power transmission lines; Propagation losses; Temperature; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32235
  • Filename
    1601837