DocumentCode :
851893
Title :
Current distribution within asymmetrical UHV bundles: A laboratory confirmation of analytical studies
Author :
West, Herschel J. ; Courts, Alan L.
Author_Institution :
Bonneville Power Administration, Portland, Oregon
Volume :
95
Issue :
4
fYear :
1976
fDate :
7/1/1976 12:00:00 AM
Firstpage :
1487
Lastpage :
1492
Abstract :
Laboratory tests confirm computer calculations of the current distribution among the subconductors of 1,100-kV bundles. The test specimen consisted of a 120-foot (36.57 m) long 8- × 1.6-inch (4 cm) Chukar conductor bundle suspended 29 feet (8.84 m) above ground at BPA´s outdoor test facility. Currents in the individual subconductors were measured at 3 degrees of bundle asymmetry. Good agreement between calculated and measured currents verifies BPA´s computer program for calculating the current distributions within conductor bundles.
Keywords :
Assembly; Computational geometry; Conductors; Contact resistance; Current distribution; Distributed computing; Fitting; Laboratories; Testing; Transmission lines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1976.32245
Filename :
1601847
Link To Document :
بازگشت