DocumentCode :
852278
Title :
Constant power factor control system for HVDC transmission
Author :
Nishimura, F. ; Watanabe, A. ; Fujii, N. ; Ogata, F.
Author_Institution :
Electric Power Development Co., Tokyo, Japan
Volume :
95
Issue :
6
fYear :
1976
Firstpage :
1845
Lastpage :
1853
Abstract :
In inverter operation of a converter for h.v.d.c. transmission, commutation failure is inevitable in such a case that a.c. voltage suddenly drops due to occurrence of a fault in the a.c. system. In this paper, the region of inevitable commutation failure is first discussed and then the constant power factor control system is proposed to squeeze the region. By using this control system, the extinction angle is kept larger in partial load than in full load. Also, the proposed control system makes it possible to rapidly increase d.c. transmission power from the minimum to full loads without controlling transformer taps.
Keywords :
Circuit faults; Control systems; Equations; Equivalent circuits; HVDC transmission; Reactive power; Short circuit currents; Thyristors; Valves; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1976.32285
Filename :
1601887
Link To Document :
بازگشت