Complete bounding method for AC contingency screening
Author :
Brandwajn, V. ; Lauby, M.G.
Author_Institution :
Syst. Control Inc., Palo Alto, CA, USA
Volume :
4
Issue :
2
fYear :
1989
fDate :
5/1/1989 12:00:00 AM
Firstpage :
724
Lastpage :
729
Abstract :
An efficient contingency screening method for detecting both branch MW flow violations and bus-voltage-limit violations is presented. The efficiency of the method stems from a bounding criterion which reduces the number of branch-flow computations and limits checking, and a bounding criterion which reduces the number of buses for which the Q-mismatch has to be calculated. The method requires no offline setup and can handle contingencies with network topology changes of any type. The method is based on the incremental angle criterion and the fast decoupled power flow. Consequently, it includes reactive power considerations
Keywords :
load flow; power systems; reactive power; AC contingency screening; bounding criterion; branch MW flow violations; bus-voltage-limit violations; fast decoupled power flow; reactive power; Control systems; Load flow; Network topology; Power engineering and energy; Power system analysis computing; Power system security; Reactive power; Stress; Testing; Voltage control;