Abstract :
The line end coil of large AC motors is known to suffer increased inter-turn voltage stress under steep fronted surge conditions. Surge capacitors can be used to slow down the surge rise-time. The effects of capacitor value and lead length on the line end coil voltage are examined. The theoretical and measured waveforms for the line end coil of a 3.3 kV, 1 MW, four-pole induction motor are compared. The results show clearly that when the capacitor lead length approaches 1, even a relatively large capacitor value has little effect
Keywords :
induction motors; power capacitors; surge protection; surges; 1 MW; 3.3 kV; AC motors; four-pole induction motor; inter-turn voltage stress; lead length; line end coil; steep fronted surge conditions; surge capacitor value; Capacitors; Coils; Induction motors; Insulation; Nose; Stress; Surge protection; Transmission line matrix methods; Transmission line measurements; Voltage;