• DocumentCode
    852995
  • Title

    Optimum shunt capacitor group fusing

  • Author

    Harder, John E.

  • Author_Institution
    Westinghouse Electric Corporation, Bloomington, Indiana
  • Volume
    96
  • Issue
    2
  • fYear
    1977
  • fDate
    3/1/1977 12:00:00 AM
  • Firstpage
    496
  • Lastpage
    501
  • Abstract
    This investigation examines the optimum selection of group fuses for shunt capacitor banks used for power factor correction on electric utility systems. The optimization is based on choosing fuse links which are as small as possible in order to minimize the probability of case rupture in event of capacitor failure, yet which are large enough to avoid nuisance melting. Increasing emphasis on safety and protection of the environment against spilled PCB´s suggest the use of a more appropriate fusing practice than a constant fusing factor or set of fusing factors. The study is based on an examination of the duty to the fuse link and an examination of the capability of fuses. Criteria for application are suggested and tables are developed for NEMA standard K & T fuse links for group fusing of shunt banks.
  • Keywords
    Circuit breakers; Fuses; Power factor correction; Power industry; Power system reliability; Power system transients; Steady-state; Switched capacitor circuits; Switches; Switching circuits;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1977.32359
  • Filename
    1601961