DocumentCode :
853008
Title :
Digital differential protection of a generating unit scheme and real-time test results
Author :
Hope, G.S. ; Dash, P.K. ; Malik, O.P.
Author_Institution :
The University of Calgary, Calgary, Canada
Volume :
96
Issue :
2
fYear :
1977
fDate :
3/1/1977 12:00:00 AM
Firstpage :
502
Lastpage :
512
Abstract :
This paper presents an on-line digital computer technique used for differential protection of a synchronous generator. It provides fault detection and tripping well within half a cycle and is also capable of discriminating between internal and external faults. In the latter case, sufficient restraint signals are generated to overcome maloperation. Further, the scheme is highly reliable even with CT saturation due to heavy through faults on the generating unit. On-line tests using a laboratory synchronous generator show the results for different types of internal and external faults with varying fault incidence inception.
Keywords :
Analog computers; Application software; Hybrid power systems; Laboratories; Power system control; Power system protection; Power system reliability; Power system simulation; Synchronous generators; Testing;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1977.32360
Filename :
1601962
Link To Document :
بازگشت