Analysis of a generator step-up transformer failure following faulty synchronization
Author :
Pasternack, Bernard M. ; Provanzana, John H. ; Wagenar, L.B.
Author_Institution :
American Electr. Power Service Corp., Columbus, OH, USA
Volume :
3
Issue :
3
fYear :
1988
fDate :
7/1/1988 12:00:00 AM
Firstpage :
1051
Lastpage :
1058
Abstract :
An analysis was carried out to investigate an out-of-phase synchronizing condition which resulted in the failure of a 725 MVA GSU (generator step-up) transformer. Using a technique described, the circuit breaker closing angle was estimated from oscillograph traces. This information was used with the Electromagnetic Transients Program (EMTP) to simulate the disturbance events and thereby produce a complete set of probable synchronizing currents and generator electrical torques experienced during the disturbance. The analysis of the simulation results, and the analysis of the failure of the GSU transformer have been viewed in light of the large number of prior system faults in the vicinity of the transformer. A review of the ANSI/IEEE standards on transformer fault withstand capabilities as related to this type of analysis is presented
Keywords :
circuit breakers; electric generators; failure analysis; power transformers; transients; 725 MVA; ANSI/IEEE standards; EMTP; Electromagnetic Transients Program; GSU transformer; circuit breaker closing angle; disturbance events; generator step-up transformer failure; out-of-phase synchronizing condition; ANSI standards; Analytical models; Circuit breakers; Circuit faults; Circuit simulation; EMTP; Failure analysis; Power generation; Rivers; Strontium;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193886
Filename :
193886
Link To Document :
بازگشت