Title :
Calculation of winding temperatures in distribution transformers subjected to harmonic currents
Author :
Hwang, M. Davis ; Grady, W. Mack ; Sanders, H. Walter, Jr.
Author_Institution :
ESCA Corp., Bellevue, WA, USA
fDate :
7/1/1988 12:00:00 AM
Abstract :
The authors compare winding temperature predictions from a finite-element-based method with actual measured values for a 10 kVA oil-immersed wire-wound single-phase distribution transformer. The results confirm the prediction algorithm and illustrate that the position of the hot spot remains basically unchanged when harmonics are present
Keywords :
finite element analysis; harmonics; power transformers; transformer windings; 10 kVA; finite-element-based method; harmonic currents; oil-immersed wire-wound single-phase distribution transformer; winding temperatures; Finite element methods; Harmonic analysis; Impedance; Petroleum; Power system analysis computing; Power system harmonics; Senior members; Temperature distribution; Testing; Transformers;
Journal_Title :
Power Delivery, IEEE Transactions on