DocumentCode :
853097
Title :
Real-time measurement approach for tracking the actual coefficient of ΔV/ΔV10 of electric arc furnace
Author :
Guan, Jin-Lung ; Gu, Jyh-Cherng ; Wu, Chi-Jui
Author_Institution :
Nat. Taiwan Univ. of Sci. & Technol., Taipei, Taiwan
Volume :
19
Issue :
1
fYear :
2004
Firstpage :
309
Lastpage :
315
Abstract :
This investigation develops a new definition of the voltage fluctuation (ΔV) electric arc furnace. Analysis of voltage flicker spectrum in the 0.25-30-Hz range reveals that the magnitude of each modulation frequency component decreases with frequency, while the standard deviation of each frequency component is high. From the statistics of electric arc furnace real time test data, the loads can be classified as weakly stationary processes, but lack a Gauss probability distribution. Traditionally, the equivalent 10-Hz voltage fluctuation (ΔV10) value can be obtained from ΔV/3.6. However, the real world tests and statistics indicate that the ratios of ΔV/ΔV10 are 1.8, not 3.6.
Keywords :
Gaussian distribution; arc furnaces; power supply quality; 0.25 to 30 Hz; Gauss probability distribution; actual coefficient; electric arc furnace; modulation frequency; power quality; real time test data; real-time measurement approach; voltage flicker spectrum; voltage fluctuation; Electric variables measurement; Frequency; Furnaces; Power systems; Probability distribution; Statistical analysis; Statistical distributions; Steel; Testing; Voltage fluctuations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2003.820182
Filename :
1256393
Link To Document :
بازگشت