Title :
Investigation of dynamic nozzle parameters for various nozzle geometries and test conditions of an experimental half-size SF6puffer breaker
Author_Institution :
General Electric Company, Philadelphia, Pennsylvania
fDate :
5/1/1977 12:00:00 AM
Abstract :
An experimental half-size puffer breaker with an insulating nozzle which is at rest during breaker opening has been used for measuring the distribution of dynamic pressure, electrical potential and ablation in the nozzle area. At the current levels used for the tests nozzle clogging can be expected. The effect of several nozzle configurations on the various measured properties has been determined for different initial pressures and magnitudes of current.
Keywords :
Area measurement; Circuit breakers; Dielectrics and electrical insulation; Electric potential; Electric variables measurement; Geometry; Pistons; Pressure measurement; Sulfur hexafluoride; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1977.32402