Abstract :
There has been much work done concerning the analytical and theoretical analysis of bus transfers, most of this pertaining to the induction motor during transients; however, very little has been published presenting experimental data of such a transfer. In this paper data is presented which was taken during and after a bus transfer on a 450 MW fossil fired unit. The data shows the validity of the models, but also indicates that the synchronous motor is more of a concern than previously thought.
Keywords :
Analytical models; Delay effects; Fault currents; Induction motors; Power engineering and energy; Power generation; Power industry; Synchronous motors; System testing; Transient analysis;