DocumentCode
853853
Title
An, RI and TVI from single unit flashover of HVDC suspension insulator strings
Author
Fukushima, Mitsuo ; Sunaga, Yoshitaka ; Sasano, Takao ; Sawada, Yoshitsugu
Author_Institution
Central Research Institute of Electric Power Industry, Tokyo, Japan
Volume
96
Issue
4
fYear
1977
fDate
7/1/1977 12:00:00 AM
Firstpage
1233
Lastpage
1241
Abstract
This paper presents the results of a study on the unusual discharge activities on dc insulators. The phenomenon, designated as "single unit flashover", completely bridges one or two insulators in a long string, and generates very high AN, RI and TVI. Since this is caused by the extreme voltage concentration on the units resulting from the thermal phenomenon on the insulator surface determined by the rate of wetting and drying, the tests were made in natural humidity conditions at the Shiobara laboratory, which has been converted to a ± 500 kV dc laboratory. This poses a serious problem for dc HV transmission design.
Keywords
Conductors; Contamination; Flashover; HVDC transmission; Humidity; Insulation; Insulator testing; Laboratories; TV interference; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1977.32446