    Application of vacuum circuit-breaker to clear faults with delayed current zeros

  • Author

    Kulick, B. ; Schramm, H.H.

  • Author_Institution
    Tech. Univ. Berlin, West Germany
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1714
  • Lastpage
    1723
  • Abstract
    In medium-voltage systems short-circuit currents with delayed zero crossings can occur either in the proximity of a concentrated generation or when switching off large high-voltage motors, or both. For two typical system configurations it is shown theoretically that vacuum circuit-breakers are well suited to clear under these conditions, provided they can withstand the high peak currents associated with such faults and their contact configuration can withstand prolonged arcing. The theoretical considerations are backed by tests. However, it will be necessary to investigate the conditions of each application to determine the actual stress upon the circuit-breaker
  • Keywords
    circuit breakers; circuit-breaking arcs; fault currents; short-circuit currents; vacuum apparatus; arcing; delayed current zeros; fault clearing; peak currents; short-circuit currents; vacuum circuit-breaker; Cables; Circuit faults; Damping; Delay; Fault currents; Frequency; Industrial plants; Medium voltage; Vacuum systems; Zero voltage switching;