Title : 
Prediction of the friction factor in laminar flow through three-phase pipe-type power transmission line
         
        
            Author : 
Koci, P.F. ; Glicksman, L.R. ; Rohsenow, W.M. ; Buckweitz, M.D.
         
        
            Author_Institution : 
Massachusetts Institute of Technology, Cambridge, Massachusetts
         
        
        
        
        
            fDate : 
7/1/1977 12:00:00 AM
         
        
        
        
            Abstract : 
The relationship between the friction factor and the Reynolds number for laminar isothermal fully developed flow through several cable configurations of a three-phase pipe-type electrical power transmission line is predicted. The predictions agree well with data taken from scaled down and full scale model tests. The RMS error is 15.4%. The friction factor varies widely among the configurations and therefore, Since the cable configuration on a real transmission system is arbitrary, the higher friction factor values found for the open triangular cable configuration should be used for design purposes.
         
        
            Keywords : 
Friction; Heat transfer; Heating; Hydraulic diameter; Petroleum; Power cables; Power system modeling; Power transmission lines; Predictive models; Testing;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/T-PAS.1977.32453