DocumentCode :
853967
Title :
Transformer model for high frequencies
Author :
Vaessen, P.T.M.
Author_Institution :
N.V. KEMA, Arnhem
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1761
Lastpage :
1768
Abstract :
A method for the development of a high-frequency transformer model for use in an electromagnetic transient program (EMTP) is discussed. A transformer to be modeled is measured, and the results are used to calculate the transfer and admittance functions. Modal analysis is used to determine a no-load network model that can be used in the EMTP. Results for a 400 kVA transformer are presented
Keywords :
electromagnetic fields; power engineering computing; transformers; 400 kVA; EMTP; HF transformer model; electromagnetic transient program; no-load network model; Damping; EMTP; Electromagnetic measurements; Electromagnetic transients; Modal analysis; Resonance; Resonant frequency; Shape measurement; Transfer functions; Vibrations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193982
Filename :
193982
Link To Document :