Title :
Some critical aspects of generator capability under unbalanced operating conditions
Author :
Blaylock, A.R. ; Hindmarsh, R. ; Foster, K.A.
Author_Institution :
C. A. Parsons & Co. Ltd., Newcastle upon Tyne, England
Abstract :
The transient negative sequence rating of a generator is discussed and I22t is concluded to be inadequate for rating the generator imbalance capability. The possible fault asymmetry, the excitation system and the duration of the fault should also be considered when rating a generator. Measurements of rotor heating during controlled tests on a large generator are discussed, and a method of calculating the loss and temperature in the main body of the rotor is examined. The calculated temperatures were in good agreement with the measurements.
Keywords :
Heating; Loss measurement; Manufacturing; Power measurement; Pressure measurement; Rotors; Stators; Temperature control; Temperature distribution; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1977.32475