DocumentCode
854162
Title
RI, TVI and AN characteristics of HVDC insulator assemblies under contaminated condition
Author
Yasui, Mitsuru ; Takahishi, Y. ; Takenaka, Akira ; Naito, Katsuhiko ; Hasegawa, Yoshio ; KATo, Kazuhisa
Author_Institution
Tokyo Electr. Power Co. Inc., Japan
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1913
Lastpage
1921
Abstract
The results of investigations into radio interference, television interference and audible noise characteristics of full-scale insulator assemblies for DC±600 kV HVDC transmission lines under contaminated and wet conditions are discussed. The interference levels during partial discharges were measured and found to be nearly the same as those as those of existing AC 500 kV transmission lines. Emphasis was placed on the characteristics of partial flashovers known as specific sparkovers under DC voltage on one or a few units in a string. The interference levels during partial flashovers were much higher than those during partial discharges. An insulator with a high flashover voltage, such as one having a diameter of 460 mm, was effective in preventing partial flashovers, at least up to a voltage of ±650 kV
Keywords
acoustic noise; flashover; insulators; partial discharges; power transmission lines; radiofrequency interference; television interference; 650 kV; AC 500 kV transmission lines; HVDC insulator assemblies; HVDC transmission lines; audible noise characteristics; contaminated condition; flashovers; partial discharges; partial flashovers; radio interference; specific sparkovers; television interference; wet conditions; Acoustic noise; Assembly; Electromagnetic interference; Flashover; HVDC transmission; Insulation; Partial discharges; TV interference; Transmission line measurements; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.194000
Filename
194000
Link To Document