Title :
Contamination performance of HVDC station post insulators
Author :
Baker, A.C. ; Zaffanella, L.E. ; Anzivino, L.D. ; Schneider, H.M. ; Moran, J.H.
Author_Institution :
Laap Insulator, Leroy, NY, USA
fDate :
10/1/1988 12:00:00 AM
Abstract :
The effect of shed configuration on the contamination performance of post insulators for HVDC converter stations is reported. Field measurements of contamination severity are used to define the contaminant levels utilized in artificial contamination tests made with the clean fog method. Test results for naturally contaminated post insulators are also presented. The influence of shape parameters on the accumulation of contaminant is also investigated by means of a dust deposit chamber. Improvements in withstand capability of post insulators with special treatments are described
Keywords :
insulation testing; insulators; HVDC converter stations; HVDC station post insulators; artificial contamination tests; clean fog method; contamination performance; shape parameters; shed configuration; withstand capability; Circuit testing; Costs; Dielectrics and electrical insulation; Flashover; HVDC transmission; Insulator testing; Pollution measurement; Shape measurement; Surface contamination; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on