Title :
Through-fault capability requirements for unit auxiliary transformers
Author_Institution :
Sargent & Lundy, Chicago, Illinois
Abstract :
The magnitude and duration of short circuit currents for faults on the low sides of unit auxiliary transformers (UATS) are calculated taking into account the generators´ initial loadings, time constants, and saturation. The stresses imposed on UATS by these currents are compared with the short circuit withstand capabilities provided by present standards. In many cases it is found that the standard capabilities are not adequate for the short circuit duties encountered in UAT applications. A method is presented to specify the short circuit withstand capabilities when the standards do not apply.
Keywords :
Circuit faults; Fault detection; Impedance; Power generation; Power transformers; Printing; Protective relaying; Relays; Short circuit currents; Stress;