Abstract :
The growing interest in very-long-distance transmission (2-3000 km) and the state of the art of half-wavelength transmission lines are briefly discussed. A model for the numerical simulation of corona losses at high electric gradients is proposed. Then an analysis is made of the steady-state and transient operation of an 800 kV, 60 Hz, 2500 km double circuit line. Results show that corona losses drastically limit the sustained overvoltages, but also place a limit on transmissible power and can affect transient stability. Possible schemes for interconnection of two half-wavelength lines at intermediate switching stations are also examined in order to attain acceptable system reliability
Keywords :
corona; losses; power transmission lines; simulation; transients; 2500 km; 60 Hz; 800 kV; corona losses; double circuit line; half-wavelength transmission lines; intermediate switching stations; reliability; simulation; steady-state operation; transient operation; transient stability; very-long-distance transmission; Analytical models; Corona; Distributed parameter circuits; Numerical models; Numerical simulation; Power system transients; Power transmission lines; Steady-state; Transient analysis; Transmission lines;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.194020
Filename :
194020
Link To Document :
بازگشت