• DocumentCode
    854379
  • Title

    A digital rate-of-change underfrequency protective relay for power systems

  • Author

    Widrevitz, B.C. ; Armington, R.E.

  • Author_Institution
    Commonwealth Edison Company
  • Volume
    96
  • Issue
    5
  • fYear
    1977
  • Firstpage
    1707
  • Lastpage
    1714
  • Abstract
    A digital relay is described for power systems application which responds both to frequency and to rate of change of frequency. Its application is in the operating situation of load suddenly in excess of generation, either because of sudden unexpected added load or because of generator or other equipment failure; and its function is the initiation of preplanned emergency load shedding. Advantages of the relay are its sensitivity to generation-load imbalance, and its relative simplicity.
  • Keywords
    Digital relays; Equipment failure; Frequency; Power generation; Power system interconnection; Power system protection; Power system relaying; Power system reliability; Protective relaying; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1977.32501
  • Filename
    1602103