DocumentCode :
854445
Title :
In service evaluation of polyethylene and crosslinked polyethylene insulated power cables rated 15 to 35 kV
Author :
Bahder, G. ; Eager, G.S., Jr. ; Suárez, R. ; Chalmers, S.M. ; Jones, W. Harold ; Mangrum, W.H.
Author_Institution :
General Cable Corporation, Union, New Jersey
Volume :
96
Issue :
6
fYear :
1977
Firstpage :
1754
Lastpage :
1766
Abstract :
This paper describes mobile inverted dissipation factor and mobile partial discharge equipment developed to measure long lengths of installed shielded power cables in the voltage range 5-35 kV. The techniques employed during field measurements and the results obtained at ten widely spaced geographical locations using this mobile equipment are presented. The field measurements are compared with laboratory measurements on portions of the cables tested. It is concluded that the mobile dissipation factor bridge equipment is an excellent tool for the detection of electrochemical trees in the cable insulation, extensively corroded concentric neutral wires and excessive conductor and insulation shield resistances. It is additionally concluded that the mobile partial discharge detector is an excellent tool for determining the existence of partial discharges of installed cable systems.
Keywords :
Cable insulation; Electrical resistance measurement; Laboratories; Length measurement; Partial discharge measurement; Partial discharges; Polyethylene; Power cables; Power measurement; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1977.32507
Filename :
1602109
Link To Document :
بازگشت