DocumentCode :
854589
Title :
Selection of 6.9 kV as voltage for east bend station auxiliaries
Author :
Reiman, R.J. ; Hatstat, C.A.
Author_Institution :
The Cincinnati Gas & Electric Company, Cincinnati, Ohio
Volume :
96
Issue :
6
fYear :
1977
Firstpage :
1882
Lastpage :
1891
Abstract :
With a new site remote from the Cincinnati Gas & Electric Company System Substations and with 650 MW units to be installed, analyses of the station auxiliary buses were made based on criteria of electrical performance, reliability, economics, engineering judgment and flexibility for future loads. The analyses confirmed the suitability and established the design parameters of a medium voltage auxiliary system which uses 6.9 kV as the nominal voltage to serve motors between 300 and 9000 hp.
Keywords :
Boilers; Circuit breakers; Medium voltage; Power generation; Power generation economics; Reliability engineering; Rivers; Strontium; Transformers; Turbines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1977.32522
Filename :
1602124
Link To Document :
بازگشت