DocumentCode :
855350
Title :
Assessment of harmonic distortion level considering the interaction between distributed three-phase harmonic sources and power grid
Author :
Ahmed, E.E. ; Xu, W.
Volume :
1
Issue :
3
fYear :
2007
fDate :
5/1/2007 12:00:00 AM
Firstpage :
506
Lastpage :
515
Abstract :
An iterative frequency domain-based harmonic analysis method for harmonic distortion assessment for systems with distributed harmonic sources has been proposed. The proposed method, unlike the traditional method, is able to consider harmonic attenuation and diversity due to the interaction between the harmonic sources and power grid. Time domain simulation for systems with distributed adjustable speed drives is used to validate the proposed method. Case studies are conducted to show the merits of the proposed method especially with a large number of distributed harmonic sources
Keywords :
power distribution faults; power system harmonics; time-domain analysis; variable speed drives; adjustable speed drives; distributed three-phase harmonic sources; harmonic distortion level; power grid; time domain simulation;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd:20060316
Filename :
4202032
Link To Document :