• DocumentCode
    855504
  • Title

    Load Modeling During Asymmetric Disturbance in a Metropolitan Power Grid

  • Author

    Xu, Wei-Hua ; Chen, Chen ; Ai, Qian ; Wang, Wei ; Ling, Xiao-Bo ; Liu, Bei ; Wang, Chong

  • Author_Institution
    Dept. of Electr. Eng., Shanghai Jiao Tong Univ., Shanghai, China
  • Volume
    24
  • Issue
    3
  • fYear
    2009
  • Firstpage
    1191
  • Lastpage
    1198
  • Abstract
    Nowadays, the measurement-based approach is one of the main methods in load modeling but it has some defects in practice, mainly, it only utilizes the data recorded during three-phase symmetric disturbances which rarely happen in power systems. In this paper load modeling during asymmetric disturbances (LMAD) is proposed. LMAD may collect data during asymmetric disturbances which occur more often in power systems. Some measured data are chosen to testify LMAD with satisfying results which not only validate the method but also are applied in power system simulation now. LMAD is promising in load modeling since it does not need extra field tests and special data acquisition instruments, both of which hardly get approval of utilities. Furthermore, the conditions on the uniqueness of identified load model parameters are discussed. Some characteristics like electromagnetic torque of the load model are studied as well.
  • Keywords
    power grids; power system measurement; power system simulation; asymmetric disturbance; data acquisition instruments; electromagnetic torque; load modeling; measurement-based approach; metropolitan power grid; power systems; three-phase symmetric disturbances; Load modeling during asymmetric disturbance (LMAD); measurement-based load modeling approach (MBLMA); power system parameter identification;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2009.2021221
  • Filename
    4914787