DocumentCode :
861209
Title :
Comparison of Voltage and Flux Modulation Schemes of StatComs Regarding Transformer Saturation During Fault Recovery
Author :
Xie, Hailian ; Ängquist, Lennart ; Nee, Hans-Peter
Author_Institution :
Sch. of Electr. Eng., R. Inst. of Technol., Stockholm
Volume :
23
Issue :
4
fYear :
2008
Firstpage :
1653
Lastpage :
1661
Abstract :
A transformer might be driven into saturation by faults in the connected system. In a transmission system with a static synchronous compensator and transformers connected at the point of common coupling, different modulation schemes utilized by the voltage source converter influence the transformer saturation in different ways. This paper compares the saturation effect during fault recovery when two alternative modulation schemes are utilized: voltage modulation and flux modulation. The comparison shows that utilization of flux modulation scheme tends to soften the saturation problem during fault recovery. However, this is achieved at a higher converter transient peak current.
Keywords :
modulation; power convertors; power transformers; power transmission faults; static VAr compensators; STATCOM; fault recovery; flux modulation schemes; saturation effect; static synchronous compensator; transformer saturation; transmission system; voltage modulation schemes; voltage source converter; Converters; StatCom; fault recovery; pulse width modulated power converters; static synchronous compensator; transformer saturation; transformers; voltage source converter (VSC);
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2008.2004725
Filename :
4624567
Link To Document :
بازگشت