Interruption of short-circuit currents in MV networks with extremely long time constants
Author
Van Den Heuvel, W.M.C. ; Janssen, A.L.J. ; Damstra, G.C.
Author_Institution
Eindhoven Univ. of Technol., Netherlands
Volume
136
Issue
2
fYear
1989
fDate
3/1/1989 12:00:00 AM
Firstpage
115
Lastpage
119
Abstract
Short-circuit testing of MV circuit breakers is usually performed according to IEC standards 56-4 with a circuit time constant of 45 ms. However, in modern MV utility and industrial networks, specific situations may be found with extremely large time constants of the DC component in the initial short-circuit current. Therefore, the actual DC component in a 3-phase short circuit-to-interrupt may be substantially larger than the breaker´s testing ratings. The authors examine the theoretical background, the influence of the DC component on interruption severity and the calculation of practical networks. A number of practical X /R and time constant values are given, and IEC and ANSI standards are compared in this respect
Keywords
circuit breakers; power system protection; short-circuit currents; switchgear testing; 45 ms; ANSI; DC component; IEC; MV circuit breakers; power system protection; short-circuit currents; standards; switchgear testing; testing ratings; time constants;
fLanguage
English