DocumentCode :
872472
Title :
Application of the duplex Reactor-an unusual and forgotten technique to reduce short circuit duty
Author :
Hamer, PAUL S.
Author_Institution :
Chevron Energy Technol. Co., Richmond, CA, USA
Volume :
42
Issue :
2
fYear :
2006
Firstpage :
612
Lastpage :
617
Abstract :
The duplex reactor is a center-tapped three-phase current-limiting reactor that can benefit power system operation when connected in certain configurations between two utility-fed distribution system buses and a local generator source. Its use was fairly common in the 1940s and 1950s. This paper discusses the physical and mutual inductance characteristics of the duplex reactor, its equivalent circuit model, and revisits its potential application to limit the three-phase short circuit duty on medium-voltage industrial systems. Its use can also result in beneficial system voltage support of local distribution buses during severe "remote" system faults. Results of simple system simulations using short circuit and load flow programs are explored on example systems.
Keywords :
current limiting reactors; equivalent circuits; short-circuit currents; center-tapped 3-phase current limiting reactor; duplex reactor; equivalent circuit model; load flow programs; local generator source; power system operation; remote system faults; short circuit duty reduction; utility fed distribution system; Circuit faults; Circuit simulation; Equivalent circuits; Inductance; Inductors; Load flow; Medium voltage; Power generation; Power system modeling; System buses; Duplex reactor; fault levels; industrial on-site generation; voltage stability;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2006.870042
Filename :
1608240
Link To Document :
بازگشت