• DocumentCode
    874711
  • Title

    Reduction of rating required for circuit breakers by employing series-connected fault current limiters

  • Author

    Calixte, E. ; Yokomizu, Y. ; Shimizu, H. ; Matsumura, T. ; Fujita, H.

  • Author_Institution
    Dept. of Electr. Eng., Nagoya Univ., Japan
  • Volume
    151
  • Issue
    1
  • fYear
    2004
  • Firstpage
    36
  • Lastpage
    42
  • Abstract
    Calculation was made to examine the reduction of the rating required for circuit breakers by using series-connected resistive and inductive fault current limiters (FCLs) under various fault locations. In the model of the inductive FCL, a capacitance Cp consisting of a coil stray capacitance and a necessary additional capacitance was taken into account. The insertion of the resistive FCL and the inductive FCL with Cp=100 nF into the power system proved to decrease the severity of the interrupting duty so that a lower-rated circuit breaker can be used. However, the introduction of the inductive FCL with Cp=10 nF was found to lessen the fault current, while raising the rate of rise of the recovery voltage. From the variation of the breaking condition, the limiting impedance required to allow a circuit breaker to perform a satisfactory interruption is discussed.
  • Keywords
    capacitance; circuit breakers; coils; electric impedance; fault current limiters; breaking condition; circuit breakers; coil stray capacitance; fault locations; interrupting duty; limiting impedance; rating reduction; recovery voltage; series-connected fault current limiters; series-connected inductive fault current limiters; series-connected resistive fault current limiters;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20040060
  • Filename
    1262762