DocumentCode
880825
Title
Accurate location of faults on power transmission lines with use of two-end unsynchronized measurements
Author
Izykowski, Jan ; Molag, Rafal ; Rosolowski, Eugeniusz ; Saha, Murari Mohan
Author_Institution
Wroclaw Univ. of Technol., Poland
Volume
21
Issue
2
fYear
2006
fDate
4/1/2006 12:00:00 AM
Firstpage
627
Lastpage
633
Abstract
This paper presents a new algorithm for locating faults on two-terminal power transmission lines. Unsynchronized two-end voltages and currents are processed for determining the sought distance to fault and the synchronization angle. The calculations are performed initially for the lumped model of a transmission line. Then, these results are used as the initial data for the Newton-Raphson method-based iterative calculations, in which the distributed parameter line model is utilized. The delivered fault location algorithm has been tested and evaluated with the fault data obtained from versatile ATP-EMTP simulations. The sample results of the evaluation are reported and discussed.
Keywords
Newton-Raphson method; fault location; lumped parameter networks; power transmission faults; power transmission lines; ATP; EMTP; Newton-Raphson method; fault location; lumped model; power transmission faults; power transmission lines; two-end unsynchronized measurements; Circuit faults; Current transformers; Fault currents; Fault location; Impedance; Phase measurement; Power measurement; Power transmission lines; Transmission line measurements; Voltage; ATP-EMTP; fault location; simulation; transmission line; two-end unsynchronized phasor measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2005.858778
Filename
1610671
Link To Document