DocumentCode :
892662
Title :
Load tap changers in emergency and preventive voltage stability control
Author :
Vournas, Costas ; Karystianos, Michael
Author_Institution :
Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
Volume :
19
Issue :
1
fYear :
2004
Firstpage :
492
Lastpage :
498
Abstract :
This paper discusses the effect of load tap changers on the voltage stability of a power system and, in particular, under emergency conditions. This discussion covers two types of load tap changers (LTCs): on bulk power delivery transformers, which are controlled automatically and for which emergency tap-reversing is considered; and on transformers between higher voltage levels, typically extra high voltage/high voltage (EHV/HV) autotransformers, that in many cases are controlled manually. An algorithm to determine taps for the latter that will maximize loadability is presented.
Keywords :
autotransformers; on load tap changers; optimisation; power system dynamic stability; power transmission control; voltage control; EHV/HV autotransformers; bulk power delivery transformers; emergency tap reversing; extra high voltage/high voltage autotransformers; load tap changers; optimization; power system; preventive control; voltage stability; Admittance; Automatic voltage control; Control systems; Induction motors; Power system control; Power system restoration; Power system stability; Power systems; Transformers; Voltage control;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2003.818728
Filename :
1266604
Link To Document :
بازگشت