DocumentCode
894131
Title
Postfault Analysis of Operation of Distance Protective Relays of Power Transmission Lines
Author
Izykowski, Jan ; Rosolowski, Eugeniusz ; Saha, Murari Mohan
Author_Institution
Wroclaw Univ. of Technol.
Volume
22
Issue
1
fYear
2007
Firstpage
74
Lastpage
81
Abstract
This paper deals with the postfault analysis of the operation of distance protective relays from the line terminals. The signals of the digital distance relays are processed in the offline regime with the aim of evaluating the particular relay operation case. First, the program enables imitating the fault-loop impedance measurements of the distance relays. Second, the two-end unsynchronized measurements of the relays are considered. The unknown synchronization angle is determined by using the developed noniterative procedure. Then, the distance to fault is calculated. It is applied for calculating the actual values of impedance for the line sections. Comparing the results of these two ways performs analysis of operation of the relays under resistive fault cases. The described postfault analysis algorithm has been tested with the fault data obtained from versatile Alternative Transients Program-Electromagnetic Transients Program simulations. The examples are reported and discussed
Keywords
EMTP; fault diagnosis; power transmission protection; relay protection; alternative transients program; digital distance relays; distance protective relays; electromagnetic transients program simulations; fault loop impedance measurements; noniterative methods; postfault analysis algorithm; power transmission lines; resistive fault cases; Algorithm design and analysis; Digital relays; Impedance measurement; Performance analysis; Power system transients; Power transmission lines; Protection; Protective relaying; Signal processing; Transient analysis; Algorithms; distance protection; fault analysis; power transmission line; simulation; two-end measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.877084