DocumentCode :
894323
Title :
Modified FBD Method in Active Power Filters to Minimize the Line Current Harmonics
Author :
Moreno, Víctor M. ; Pigazo, Alberto
Author_Institution :
Dept. of Electron. & Comput., Cantabria Univ., Santander
Volume :
22
Issue :
1
fYear :
2007
Firstpage :
735
Lastpage :
736
Abstract :
Harmonic line currents due to nonlinear loads cause nonsinusoidal grid voltages in electrical power systems. Shunt active power filters (SAPFs) can be employed to improve the system efficiency but their design must consider nonsinusoidal conditions. The Fryze, Buchholz, and Depenbrock method has been applied to controllers in SAPFs, allowing the compensation of the load nonactive power. A drawback of this method is a resultant line current with harmonic components which contributes to maintain the grid voltage distortion. This letter proposes a new definition of conductance for SAPF controllers in case of nonlinear loads and nonsinusoidal grid voltages which minimize the line current distortion
Keywords :
active filters; power grids; power harmonic filters; Fryze Buchholz Depenbrock method; electrical power systems; grid voltage distortion; harmonic components; line current harmonics minimization; load nonactive power; nonlinear loads; nonsinusoidal grid voltages; resultant line currents; shunt active power filter controller; Active filters; Frequency; Harmonic distortion; Helium; Power harmonic filters; Power system harmonics; Power system measurements; Reactive power; Total harmonic distortion; Voltage control; Harmonic distortion; power system harmonics; power systems;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.886769
Filename :
4039454
Link To Document :
بازگشت