• DocumentCode
    901352
  • Title

    A graphical approach to hydrogenerator governor tuning

  • Author

    Wozniak, L.

  • Author_Institution
    Dept. of Gen. Eng., Illinois Univ., Urbana, IL, USA
  • Volume
    5
  • Issue
    3
  • fYear
    1990
  • fDate
    9/1/1990 12:00:00 AM
  • Firstpage
    417
  • Lastpage
    421
  • Abstract
    A graphical approach to hydrogenerator governor tuning is described. A graph which is developed can be used to predict optimum proportional and integral gains based on four parameters: the time constants of the water column and of the rotor inertia, and the self-regulation constants of the turbine and of the loading grid. The pole cancellation method of design is used, and the results are posed in an easy-to-use format that does not require the solution of systems of equations. Information on stability limits and comparisons with other work are included
  • Keywords
    hydroelectric generators; self-adjusting systems; stability; three-term control; PID control; graphical approach; hydrogenerator governor tuning; integral gains; loading grid; pole cancellation method; proportional gains; rotor inertia; self-regulation constants; stability limits; turbine; water column time constants; Design methodology; Equations; Frequency; Pressure control; Proportional control; Stability; Three-term control; Torque control; Turbines; Velocity control;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.105263
  • Filename