Title :
Passive filters - potentialities and limitations
Author_Institution :
AMEC E&C Services Inc., Decatur, GA, USA
Abstract :
New topologies for harmonic mitigation and active filters have come a long way, and these address the line-harmonic control at the source. These mitigate some of the disadvantages of passive filters, however, for nonlinear loads above 1 MW the passive filters are an economical choice. This paper discusses two types of filters: band pass filters and damped filters, which are commonly applied. The operation of these filters is described with respect to the design and system limitations. The operating constraints are then superimposed. The development of this approach shows that there are design limitations and large system changes or modifications can result in higher distortion or even damage to filters in extreme cases. The constraints and limitations that a designer faces in implementing an effective filter design with modern tools of harmonic analysis, measurements, and system analysis are discussed. The paper shows that in most distribution systems it is practical and economical to implement passive filter designs, provided the required safeguards are considered.
Keywords :
band-pass filters; distortion; harmonic analysis; harmonics suppression; passive filters; power harmonic filters; 1 MW; band pass filter; damped filter; distortion; filter design; harmonic mitigation; nonlinear loads; passive filter; Active filters; Band pass filters; Frequency; Harmonic analysis; Low pass filters; Passive filters; Power generation economics; Power harmonic filters; Reactive power; Voltage;
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :
10.1109/TIA.2003.821666