DocumentCode :
902755
Title :
Resonance Overvoltages in Medium-Voltage Multilevel Drive Systems
Author :
Endrejat, Frieder ; Pillay, Pragasen
Author_Institution :
Sasol Technol., Secunda, South Africa
Volume :
45
Issue :
4
fYear :
2009
Firstpage :
1199
Lastpage :
1209
Abstract :
Simulations and field tests indicate that unacceptable motor-terminal overvoltages and waveform shapes can occur in the normal operating range with high-output-voltage multilevel drive systems. These waveforms (if unattended) can result in premature motor insulation failures. A case study of an 11-kV multilevel system is presented. Simulations and calculations confirm the theory of resonance overvoltages. Different solution possibilities are analyzed. Further simulations and investigations are performed to determine the optimal carrier frequency. Test results confirm that the proposed modification has the desired effect, with waveforms well within limits stipulated by international standards. Simplified equations and recommendations are provided to determine suitable application solutions. Further simulated resonance case studies are presented, considering the effect of the system configurations, motor size, and cable length. Suitable carrier-frequency selection methods are presented to solve the problem.
Keywords :
AC motor drives; machine protection; overvoltage protection; AC motor drives; carrier-frequency selection; equivalent circuits; harmonic analysis; load modeling; medium voltage multilevel drive systems; motor terminal overvoltage; resonance overvoltage; rotating machine testing; voltage 11 kV; AC motor drives; equivalent circuits; harmonic analysis; load modeling; medium voltage (MV); overvoltage protection; resonance; rotating machine testing;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2009.2023482
Filename :
4957045
Link To Document :
بازگشت