• DocumentCode
    904601
  • Title

    Fault location for transmission lines with current-transformer saturation

  • Author

    Richards, G.G. ; Tan, O.T.

  • Author_Institution
    Louisiana State University, Department of Electrical Engineering, Baton Rouge, USA
  • Volume
    130
  • Issue
    1
  • fYear
    1983
  • fDate
    1/1/1983 12:00:00 AM
  • Firstpage
    22
  • Lastpage
    27
  • Abstract
    The paper presents a fault-location method which is insensitive to current-transformer saturation. The method requires less than one cycle of recorded fault data, which do not need filtering. A parameter estimation technique is applied where the linear part of the reference model response is described by instantaneous symmetrical components and the nonlinear part, caused by transformer saturation, described by phase variables. The parameters identified by the estimator are fault distance, fault resistance and saturation parameters. Accuracy is demonstrated by digital simulation studies.
  • Keywords
    current transformers; digital simulation; fault location; power transmission lines; current-transformer saturation; digital simulation; fault distance; fault resistance; fault-location method; parameter estimation technique; saturation parameters; transmission lines;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1983.0004
  • Filename
    4643570