• DocumentCode
    905210
  • Title

    Improved input signals to the polarised-mho distance relay

  • Author

    Cook, V.

  • Author_Institution
    University College, Department of Electrical and Electronic Engineering, Cardiff, UK
  • Volume
    130
  • Issue
    4
  • fYear
    1983
  • fDate
    7/1/1983 12:00:00 AM
  • Firstpage
    206
  • Lastpage
    216
  • Abstract
    The paper examines the polarising signals used in British and Continental distance protection schemes, in an attempt to optimise the resistive reach of the polarised-mho relay, and also minimise the possibility of overreaching during zone 2 resistive faults. Dual and single polarisation schemes are investigated and alternative schemes with improved protection characteristics are suggested. Relay performance, during `reverse¿¿ phase-to-phase faults, is considered, and a simple procedure is given to establish a relay characteristic for a `reverse¿¿ fault.
  • Keywords
    electrical faults; relay protection; relays; distance protection schemes; faults; input signals; performance; polarised-mho distance relay; polarising signals;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1983.0034
  • Filename