DocumentCode :
906182
Title :
Injected currents of controlled AC/DC converters for harmonic analysis in industrial power plants
Author :
Grotzbach, M. ; Frankenberg, Wolfgang
Author_Institution :
Dept. of Electr. Eng., Univ. of Federal Defence, Munich, Germany
Volume :
8
Issue :
2
fYear :
1993
fDate :
4/1/1993 12:00:00 AM
Firstpage :
511
Lastpage :
517
Abstract :
An easy method for predetermining the injected current harmonics of current-controlled six-pulse bridge converters is proposed. The parameters considered are the operating point of the converter, given by the DC mean current Id and EMF E, and two circuit parameters, AC network and DC reactance. When starting the predetermination, the operating point and the effective DC reactance have to be determined from the requirements of the applied DC loads. This leads to a uniform investigation of the controlled converter based on preliminary investigation reported elsewhere. As a result of systematic evaluations, the normalized line current harmonics are obtained graphically in the usual range of the parameters considered
Keywords :
bridge circuits; electric reactance; harmonics; power convertors; power plants; AC network reactance; DC mean current; DC reactance; controlled AC/DC converters; harmonic analysis; industrial power plants; normalized line current harmonics; six-pulse bridge converters; Circuits; DC-DC power converters; Harmonic analysis; Industrial control; Load flow analysis; Power generation; Power system harmonics; Pulse power systems; Steady-state; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.216853
Filename :
216853
Link To Document :