DocumentCode :
906262
Title :
Modeling of the Hydro-Quebec-New England HVDC system and digital controls with EMTP
Author :
Morin, G. ; Bui, L.X. ; Casoria, S. ; Reeve, J.
Author_Institution :
Hydro-Quebec, Montreal, Que., Canada
Volume :
8
Issue :
2
fYear :
1993
fDate :
4/1/1993 12:00:00 AM
Firstpage :
559
Lastpage :
566
Abstract :
The commissioning of the Quebec-New England multiterminal DC transmission system underscores the increasing need to develop numerical models for simulation purposes. The modern microprocessor-based HVDC (high-voltage direct-current) converter controls used in this scheme make the modeling a real challenge since the Electromagnetic Transient Program (EMTP), usually employed for simulation purposes, and Transient Analysis of Control Systems (TACS) were designed to simulate analog, not digital controls. Details on the modeling of digital controls with a modified EMTP version are given. Some comparisons with HVDC (high-voltage direct current) simulator results which show good agreement between the two power system analysis tools are presented. A case that is validated with field test results is also included
Keywords :
DC power transmission; digital control; power convertors; power system computer control; power system interconnection; EMTP; Electromagnetic Transient Program; Hydro-Quebec-New England HVDC system; Transient Analysis of Control Systems; digital controls; high-voltage direct-current; microprocessor-based convertor controls; multiterminal DC transmission system; Analog-digital conversion; Analytical models; Digital control; EMTP; Electromagnetic modeling; HVDC transmission; Numerical models; Numerical simulation; Power system modeling; Power system simulation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.216860
Filename :
216860
Link To Document :
بازگشت