• DocumentCode
    906351
  • Title

    Utilizing HVDC to damp power oscillations

  • Author

    Smed, T. ; Andersson, G.

  • Author_Institution
    Dept. of Electr. Power Syst., R. Inst. of Technol., Stockholm, Sweden
  • Volume
    8
  • Issue
    2
  • fYear
    1993
  • fDate
    4/1/1993 12:00:00 AM
  • Firstpage
    620
  • Lastpage
    627
  • Abstract
    Damping of slow oscillations with active and reactive power modulation of high-voltage direct current (HVDC)-links is analyzed with the aim of gaining a physical insight into the problem. The analysis shows that active power modulation is efficient when applied a short mass-scaled electrical distance from one of the swinging machines, and reactive power modulation is most efficient when a well-defined power flow direction exists and the modulation is made at a point close to the electrical midpoint between the swinging machines. It is shown that the intuitively appealing feedback signal frequency and derivative of the voltage are appropriate for active and reactive power modulation. The impact of the constraints imposed by the HVDC equations is analyzed, and it is determined when the implicit reactive power modulation resulting from constant γ control may be detrimental for the damping
  • Keywords
    DC power transmission; damping; oscillations; reactive power; HVDC; active power modulation; feedback signal frequency; high-voltage direct current; power flow direction; power oscillations damping; reactive power modulation; short mass-scaled electrical distance; swinging machines; Damping; Eigenvalues and eigenfunctions; HVDC transmission; Power system analysis computing; Power system control; Power system modeling; Power system stability; Power systems; Reactive power; Stability analysis;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.216868
  • Filename
    216868