DocumentCode :
906417
Title :
Estimation of lightning current wave front duration by the lightning performance of Japanese EHV transmission lines
Author :
Udo, T.
Author_Institution :
Denryoku Comput. Center Ltd., Tokyo, Japan
Volume :
8
Issue :
2
fYear :
1993
fDate :
4/1/1993 12:00:00 AM
Firstpage :
660
Lastpage :
671
Abstract :
In the analysis of back-flashover of transmission lines, the wave-front time of the lightning current is assumed to be 2~4 μs. The results of a lightning investigation at the tops of isolated towers show that the front time is closely related to the current amplitude, and is longer than 8 μs in 70~120 kA range. The author estimates the wave-front time from the lightning performance of EHV (extra-high-voltage) double circuit transmission lines, and finds that it is about 4 μs in the 70~150 kA range. The author predicts that lightning currents measured at the tops of isolated tall towers will be different in shape because of the large predischarge current
Keywords :
flashover; lightning; poles and towers; power overhead lines; 2 to 8 mus; 70 to 150 kA; Japanese EHV transmission lines; back-flashover; current amplitude; double circuit transmission lines; extra-high-voltage; isolated towers; lightning current wave front duration; predischarge current; Distributed parameter circuits; Lightning; Performance analysis; Poles and towers; Power & Energy Society; Power transmission lines; Printing; Shape; Steel; Surges;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.216873
Filename :
216873