    Measuring molded case circuit breaker resistance

  • Author

    Shea, John J. ; Bindas, John A.

  • Author_Institution
    Westinghouse Sci. & Technol. Center, Pittsburgh, PA, USA
  • Volume
    16
  • Issue
    2
  • fYear
    1993
  • fDate
    3/1/1993 12:00:00 AM
  • Firstpage
    196
  • Lastpage
    202
  • Abstract
    Measurements of molded case circuit breaker resistance under various conditions carried out to demonstrate the need for more standardized procedures when performing millivolt drop measurements are discussed. Breakers rated at 600 Vac/250 Aac and 120/240 Vac/50 Aac, with silver-tungsten contacts, were used to show that contact resistance can cause variability in circuit breaker resistance. They were also used to demonstrate the unique influence that current, time, contact temperature, and applied voltage each had on contact resistance. Based on these results, guidelines were developed for improving the reliability of the millivolt drop test
  • Keywords
    circuit breakers; contact resistance; electric resistance measurement; electrical contacts; silver; tungsten; 120 V; 240 V; 250 A; 50 A; 600 V; Ag-W contacts; applied voltage; contact resistance; contact temperature; current effect; millivolt drop measurements; molded case circuit breaker resistance; reliability; resistance measurement; time effect; Circuit breakers; Circuit testing; Computer aided software engineering; Contact resistance; Electrical resistance measurement; Guidelines; Heating; Performance evaluation; Temperature; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Components, Hybrids, and Manufacturing Technology, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0148-6411
  • Type

    jour

  • DOI
    10.1109/33.219405
  • Filename
    219405