• DocumentCode
    915707
  • Title

    Separable insulated connector loadbreak testing. II. Providing reliability assurances

  • Author

    Filter, R. ; Mintz, J.D.

  • Author_Institution
    Ontario Hydro, Toronto, Ont., Canada
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    560
  • Lastpage
    566
  • Abstract
    For pt.I see ibid., vol.7, no.2, p.554-9 (1992). A statistical analysis of the ANSI/IEEE loadbreak switching test shows that it cannot offer utilities reliability assurances. An alternative approach to loadbreak testing is presented. It utilizes the concepts of a generic switching reliability characteristic, composite system switching reliability (CSSR), and lower confidence limits to relate laboratory test performance to utility reliability needs
  • Keywords
    electric connectors; reliability; switching; testing; ANSI/IEEE loadbreak switching test; composite system switching reliability; generic switching reliability characteristic; insulated connector loadbreak testing; loadbreak testing; reliability; statistical analysis; Connectors; Filters; Insulation; Interconnected systems; Laboratories; Power system reliability; Silicon carbide; Statistical analysis; Switches; Testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.127049
  • Filename
    127049