Magnification of transient voltages in multi-voltage-level, shunt-capacitor-compensated, circuits
Author :
Dunsmore, Dawn M. ; Taylor, Edgar R. ; Wirtz, Bernard F. ; Yanchula, T.L.
Author_Institution :
ABB Power Syst. Inc., Pittsburgh, PA, USA
Volume :
7
Issue :
2
fYear :
1992
fDate :
4/1/1992 12:00:00 AM
Firstpage :
664
Lastpage :
673
Abstract :
The transient response of two, three, and four series L- C loop systems is examined, and results are presented of a case study of voltage magnification on an actual system with shunt capacitors at four different voltage levels. On this system, equipment damage occurred within an industrial plant in the same time frame of the energization of a capacitor bank in a utility substation
Keywords :
capacitor storage; compensation; power systems; substations; transient response; L-C loop systems; capacitor bank; equipment damage; multi-voltage-level; power systems; shunt-capacitor-compensated; transient response; transient voltages; utility substation; voltage magnification; Capacitors; Circuits; Frequency; Industrial plants; Industrial power systems; Power system transients; Substations; Surges; Transient analysis; Voltage;