DocumentCode :
916388
Title :
Calculation techniques and results of effects of GIC currents as applied to large power transformers
Author :
Girgis, Ramsis S. ; Ko, Chung-Duck
Author_Institution :
ABB Power T&D Co. Inc., Muncie, IN, USA
Volume :
7
Issue :
2
fYear :
1992
fDate :
4/1/1992 12:00:00 AM
Firstpage :
699
Lastpage :
705
Abstract :
Techniques for calculating overheating effects of GIC (geomagnetically induced currents) on large shell-form transformers are described. The techniques include: the method of calculating the exciting current and its harmonic content under DC injection in the transformer neutral; three-dimensional magnetic flux calculation; circulating current calculation, loss calculation due to these currents; and temperature rise calculation. These methods are applied to two large shell-form transformers of different design. One of them suffered severe GIC effects and had burnt coils. The other one did not suffer noticeable GIC effects. These methods also show that the more recent transformer (the sound unit) tolerates about six times higher GIC current than the older unit (the first unit)
Keywords :
losses; magnetic flux; power transformers; DC injection; circulating current calculation; geomagnetically induced currents; loss calculation; overheating effects; power transformers; shell-form transformers; temperature rise calculation; three-dimensional magnetic flux calculation; transformer neutral; Coils; Gases; Geometry; Inductance; Magnetic analysis; Magnetic cores; Petroleum; Power transformers; Temperature; Transformer cores;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.127070
Filename :
127070
Link To Document :
بازگشت