DocumentCode :
917464
Title :
Distribution feeder modification to service both sensitive loads and large drives
Author :
Morgan, Larry ; Ihara, Satoru
Author_Institution :
Duke Power Co., Charlotte, NC, USA
Volume :
7
Issue :
2
fYear :
1992
fDate :
4/1/1992 12:00:00 AM
Firstpage :
883
Lastpage :
887
Abstract :
An intermittent load consisting of large adjustable speed drives had to be added to an existing 24 kV feeder for office buildings equipped with computers of various types. A standard option of constructing a new substation or a new transmission feeder was not possible due to environmental concerns. Consequently, the existing feeder had to be modified through innovative application of a specially designed harmonic filter and a distribution series capacitor so that harmonic problems, voltage flicker problems, and commutation notch problems could be avoided. The technical aspects of the problems and solutions are presented. In addition, the cooperation required between the utility and the customer is discussed
Keywords :
distribution networks; filters; harmonics; variable speed drives; 24 kV; adjustable speed drives; commutation notch problems; distribution feeder modification; distribution series capacitor; harmonic filter; harmonic problems; intermittent load; sensitive loads; voltage flicker problems; Capacitors; Commutation; Drives; Power quality; Reactive power; Substations; Test facilities; Transformers; Varistors; Voltage fluctuations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.127094
Filename :
127094
Link To Document :
بازگشت